Transmitters for flood monitoring

Sensors are not included and must be ordered separately.
GC60F The GenII flood sensing system consists of the battery powered GC60F transmitter to which one or two flood sensing cables can be connected. Each flood sensing cable assembly consists of two sections: an inactive section and an active section. The active section of the cable is an exposed pair of steel wires twisted about a black and yellow flat pair, forming a continuous 4 core twist. The exposed steel wires perform the flood detection. The black and yellow wires have no functional use but serve to make the cable easily recognisable so that it is less likely to be confused with other alarm or wiring installations.

The GC60F transmits a "1.0" to indicate OK and a "0.0" to indicate that wetness or flood is detected. This value is recorded by the logger. The system does not provide an indication of the severity of wetness or flooding.
The Darca software can be configured to alarm if a "0.0" condition is detected. This in turn can generate a SMS text message, local audible and/or visual alarm or trigger an autodialler.
GC-60F

Sensors

LC-Leak15/4 Leak sensing cable with 15m inactive section and 4m active section. For other combinations the flood sensing cables can be made to order.

To order use the following code: GC60F / AxaM / AyaM / BxbM / BybM where:
xa = length in metres of cable A’s inactive section
ya = length in metres of cable A’s active section
xb = length in metres of cable B’s inactive section
yb = length in metres of cable B’s active section
(insert “0” if Not required)

Accessories

Common Specification

RF specification: EN300-220
RF power: 10mW
Environment specification  
  Compliant to EN300-220: -10 to +55°C
  Actual: -30 to +65°C
  Humidity: 100% non condensing
Environmental rating: IP40
Dimensions (footprint): 78 x 41mm
Battery endurance: up to 5 years (interval set to 5 minutes) (less for GL-70 and GS40 series)
Transmission interval range: 1 sec to 4 hours
Indicator (red LED): transmit active/on/off
Control switch (concealed): test mode / hibernate
Antenna socket: SMA

Transmitter Specification

Active section of cable  
  Diameter: 3.4mm
  Length limit: 10m
Inactive section of cable  
  Length limit: 10m

Common to all transmitters
Gen II Quick Start Instructions

Specific to this family of transmitters
Datasheet
Flood transmitter leaflet